Search results will appear here

JB-YCY

  • REACH
  • RoHS
  • CE
JB-YCY
JB-YCY-Cross

Application

For use as a data and control cable in machinery, computer systems etc. as well as a signal cable for electronics. The high level of screening ensures a high degree of interference protection. The dense screening assures disturbance-free transmission of all signals and impulses. The PVC-inner sheaths of these cables raise the mechanical strength. The applied clear transparent PVC outer sheath accentuates the optical view of the tinned copper braid. These cables are suitable for flexible use for medium mechanical stresses with free movements.

Standard

Adapted to DIN/BS EN 50525-2-51.

Technical Data

Nominal Voltage: Uo / U 300 / 500V up to 1.5 mm². Uo / U 450 / 750V for 2.5 mm² and above

Insulation Resistance: Min. 20 GΩ x cm

Temperature Range: Flexing -5°C to +70°C. Fixed installation -30°C to +70°C

Minimum Bending Radius: Flexing 20 x cable ø. Fixed installation 6 x cable ø

Test Voltage: 4000V

Breakdown Voltage: Min. 8000V

Mutual Capacitance (0.5 to 2.5 Sq. mm): core to core (approx.) – 150 nF/km

core to screen (approx.) – 270 nF/km

Cable Construction

Bare copper, fine wire conductors, EN 60228 Cl. 5.
Core insulation of TI2, EN 50363-3.
Core identification : As per VDE 0293-302/HD 308 S2 (Refer appendix table No. 1-1)
Green/yellow earth core in outer layer (3 cores and above).
Cores stranded in layers with optimal lay-length.
Special PVC inner jacket.
Tinned copper, braided screen, approx 85% coverage.
Transparent special PVC outer sheath.

Properties

PVC self-extinguishing and flame retardant according to EN 60332-1-2.

EMC: Electromagnetic compatibility

To optimise the EMC features we recommend a large round contact of the copper braiding on both ends.

Cable Design Parameters

Part NumberNo. of Cores and Nominal
Cross Sectional Area (Sq. mm)
Approx. Cable
Diameter (mm)
Approx. Copper
Weight (kg/km)
Approx. Cable
Weight (kg/km)
0306010102162 x 0.57.937124
0306010201163G 0.58.344139
0306010301164G 0.58.853168
0306010401165G 0.59.660205
0306010501167G 0.510.276243
0306010602162 x 0.758.344140
0306010701163G 0.758.754160
0306010801164G 0.759.566198
0306010901165G 0.7510.178239
0306011001167G 0.7510.899286
0306011102162 x 18.653156
0306011201163G 19.265182
0306011301164G 19.879221
0306011401165G 110.794272
0306011501167G 111.5122328
0306011602162 x 1.59.766198
0306011701163G 1.510.287231
0306011801164G 1.511.1106286
0306011901165G 1.512.4129368
0306012001167G 1.513.2165442
0306012102162 x 2.511.295271
0306012201163G 2.511.8126318
0306012301164G 2.513.1159412
0306012401165G 2.514.3193511
0306012501167G 2.515.4257624
0306012601164G 413.4264565
0306012701165G 414.8317697
0306012801164G 615.6365732
0306012901165G 617442909
0306013001163G 1017.8453889
0306013101164G 1019.75801125
0306013201165G 1021.67111408
0306013301163G 1620.77071274
0306013401164G 1622.69171618
0306013501165G 1625.211282047
0306013301163G 2526.310641965
0306013401164G 2528.913862512
0306013501165G 2531.817083153
0306013601163G 3529.414532554
0306013701164G 3532.219003259
0306013801165G 3536.023474133
0306013901163G 5035.120483653
0306013801164G 5038.826884701
0306013901164G 7043.737326229
0306014001164G 9550.449158123
0306014101164G 12056.8619810118
0306014201164G 15062.2760012511
0306014301164G 18567.8933415306

Note:

  • *JB = With green/yellow earth core
  • OB = Without green/yellow earth core
  • For current ratings to DIN VDE 0298-4 refer table no. 12-3 of Appendix.