JB-H

  • REACH
  • RoHS
  • CE
JB-H
JB-H Cross

Application

Halogen-free cables for airports railway station, plant engineering and Industrial machinery

Standard

Adapted to EN 50525-3-11

Technical Data

Nominal Voltage: UO / U 450 / 750V

Temperature Range: Flexing -15°C to +70°C. Fixed installation -30°C to +70°C

Minimum Bending Radius: Flexing approx. 15 x cable ø. Fixed installation approx. 4 x cable ø

Test Voltage: 3000V

Cable Construction

Bare copper, fine wire conductors, to EN 60228 Cl. 5.

Core insulation of halogen-free compound TI6 to EN 50363-7.

Colour coded to DIN VDE 0293-308 (Refer Appendix Table No. 1-1).

Green/Yellow earth core in outer layer.

Cores stranded in layers with optimal lay-length.

Halogen-Free sheath compound TM7, to EN 50363-8.

Sheath colour grey (RAL 7001).

Properties

Flame retardant to IEC 60332-1-2.

No flame propagation according to IEC 60332-3-24 (flame spread on Vertical cable or wire bundle).

Halogen free according to IEC 60754-1.

Corrosive gas evolution to IEC 60754-2.

Cabel Design Parameters

Part NumberNo. of Cores & Nominal
Cross Sectional Area (Sq. mm)
Approx. Cable
Diameter (mm)
Approx. Copper
Weight (kg/km)
Approx. Cable
Weight (kg/km)
0317003111053 G 1.58.238.2110
0317004111054 G 1.58.950.9135
0317005111055 G 1.51063.7169
0317003112053G 2.51063.7169
0317004112054G 2.510.984.9209
0317005112055G 2.512106.1256
0317003100043G 411.2101.2231
0317004100044G 412.5135295
0317005100045G 413.9168.7366
0317004100064G 614202.4398
0317005100065G 615.5253.1492
0317004100104G 1017.4344.7642
0317005100105G 1019.4430.8800
0317004100164G 1620.2574.1959
0317005100165G 1622.5717.71194
0317004100254G 2525.1893.11486
0317005100255G 2528.11116.31860
0317004100354G 3528.61257.62013
0317005100355G 3532.115722525
0317004100504G 5033.91804.42860
0317004100704G 7039.22549.73940
0317004100954G 9544.83399.75205
0317004101204G 12050.34306.26579

Note:

  • *G = With green/yellow earth core
  • For current ratings conversion factors, refer table no. 11-3 of Appendix.
  • For current ratings to DIN VDE 0298-4 refer table no. 12-3 of Appendix.