Halogen-Free H07Z-R-6491B

  • REACH
  • RoHS
  • CE
  • CPR Compliant
HALOGEN-FREE H07Z-R-6491B Wire
HALOGEN-FREE H07Z-R-6491B Cross

Application

The cables are suitable for conduit wiring , especially in installations where fire, smoke and toxic fumes create potential threat.

Standard

BS EN 50525-3-41.

Technical Data

Voltage Rating: Uo / U – 450 / 750V

Harmonised Designation: 1.5 mm² to 630 mm² stranded class 2 – H07Z-R

Temperature Range: -15°C to 90°C

Minimum Bending Radius: Upto 10 mm² : 3 X Overall Diameter. 16 & 25 mm² : 4 X Overall Diameter. Above 25 mm² : 5 X Overall Diameter.

Cable Construction

Conductor: Plain annealed copper conductor 1.5 mm² to 630 mm² stranded Cl. 2 complying with EN 60228

Insulation: LSZH (Low Smoke Zero Halogen) Type EI5 according to BS EN 50363-5

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green / yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.

Part NumberNominal Cross
Sectional Area
(Sq. mm)
Nominal
Insulation
Thickness (mm)
Overall Diameter
Lower Limit
(mm)
Overall Diameter
Upper Limit
(mm)
Approx. Net
Weight (kg/km)
01130101xx601.50.702.703.4019
01130102xx602.50.803.304.1033
01130103xx6040.803.804.7050
01130104xx6060.804.305.4074
01130105xx60101.005.607.00126
01130106xx60161.006.408.00184
01130107xx60251.208.1010.10295
01130108xx60351.209.0011.30375
01130109xx60501.4010.6013.20510
01130110xx60701.4012.1015.10710
01130111xx60951.6014.1017.60950
01130112xx601201.6015.6019.401240
01130113xx601501.8017.3021.601530
01130114xx601852.0019.3024.101800
01130115xx602402.2022.0027.502500
01130116xx603002.4024.5030.602990
01130117xx604002.6027.5034.303860
01130118xx605002.8030.5038.204900
01130119xx606302.8034.0042.506370
  • For current ratings refer table no. 9-1 & voltage drop refer table no. 9-2.

*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)