H05Z1-K & H07Z1-K

  • REACH
  • RoHS
  • CE
H05Z1-K & H07Z1-K
H05Z1-K & H07Z1-K-Cross

Application

Halogen-free single-core wires are used for installation in dry environments for wiring up lighting fixtures and units where valuable assets are to protected from further damage resulting from fire. These cables may be installed on, in and beneath plaster, as well as in closed installation ducts. For use in public places such as: hospitals, schools, museums, airports, bus terminals, shops in general, etc., as well as in computer rooms, offices, production plants, switchboard wiring, laboratories, etc.

Standard

BS EN 50525-3-31.

Technical Data

Nominal Voltage : H05Z1- K Uo / U 300 / 500V; H07Z1- K Uo / U 450 / 750V

Harmonized Designation : 0.5 mm² to 1 mm² – H05Z1- K, 1.5 mm2 to 240 mm2 – H07Z1- K

Temperature Range : -30°C to +70°C

Minimum Bending Radius :

Cable diameter ≤ 8 mm: 4 x outer diameter

Approx. diameter > 8 to 12 mm: 5 x outer diameter

Approx. diameter > 12 mm: 6 x outer diameter

Test Voltage: 2500V

Cable Construction

Conductor Class 5 flexible plain / metal coated stranded according to EN 60228.

Insulation of thermoplastic halogen-free compound type TI7 to EN 50363-7.

Properties

  • Smoke density to acc. to EN 61034-2.
  • Halogen free acc. to EN 50525-1, EN 60754-1.
  • Corrosivity acc. to EN 60754-2.
  • Ozone resistant according to EN 60811-2-1 or HD 505.2.1.
  • Self-extinguishing and flame retardant according to EN 60332-1-2.
  • LSOH = Low Smoke Zero Halogen.

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink,
12 – grey.
By adding the suffix (in place of ‘c’) for the conductor type required:
0 = Annealed Bare Copper (ABC), 1 = Annealed Tinned Copper (ATC).

Part NumbersNominal Cross
Sectional Area
(Sq. mm)
Nominal Thickness
of Insulation
(mm)
Mean Overall Diameter
Approx. Cable
Weight
(kg/km)
Lower Limit (mm)Upper Limit (mm)
H05Z1-K02050101xx7c0.50.62.12.59.5
02050102xx7c0.750.62.22.712.5
02050103xx7c10.62.42.815.5
H07Z1-K02050104xx7c1.50.72.83.421.5
02050105xx7c2.50.83.44.133.5
02050106xx7c40.83.94.848
02050107xx7c60.84.45.367
02050108xx7c101.05.76.8113
02050109xx7c161.06.78.1171
02050110xx7c251.28.410.2262
02050111xx7c351.29.711.7360
02050112xx7c501.411.513.9513
02050113xx7c701.413.216.0705
02050114xx7c951.615.118.2931
02050115xx7c1201.616.720.21175
02050116xx7c1501.818.622.51264
02050117xx7c1852.020.624.91783
02050118xx7c2402.223.528.42341
  • For current ratings refer table no. 7-1.