Search results will appear here

EHV Power Cable

  • REACH
  • ROHS
  • CE
EHV-001
EHV-002
EHV-003

Cable Construction

Conductor: Stranded Compact Circular Aluminium as per Class 2 of IS 8130

Conductor Screening: Extruded Semiconductor Compound

Insulation Material: XLPE (Cross linked Polyethylene)

Insulation Screening: Extruded Semiconducting Compound

Water Blocking: Water Swellable Tape

Metallic Sheath: Corrugated Aluminium Sheath followed by Anit corrosive layer

Outer Sheath: Extruded PE as per IS 7098-3

Standard

IS 7098 Part 3

Voltage Grade

38 / 66 (E)

Cable Technical Data

Dimension

Nominal Size Of Conductor (Sq.MM)Nominal insulation thickness (mm)Min. Aluminium Sheath thickness (mm)Nominal Outersheath thickness (mm)Approx. overall diameter (mm)
95111.82.5265
120111.82.5265
150111.82.5267
185111.82.5268
240111.92.6870
300111.92.6871
400112.02.8474
500112.12.8476
630112.2380

Electrical Parameters

Nominal size of conductor (sq.mm)Trefoil SPB/CB Aluminium Ground (Amp)Trefoil SPB/CB Aluminium Air (Amp)Flat SPB/CB Aluminium Ground (Amp)Flat SPB/CB Aluminium Air (Amp)Fault rating of Aluminium sheath (kA/1 sec)Maximum capacitance (uf/km)REactance (Ohms/Km)Conductor short CKT rating (kA/1 sec
9520526520529531.50.140.1438.98
12023030523534031.50.150.13711.34
15025534526538531.50.160.13414.17
18529039530544031.50.170.12817.48
24033546034552031.50.190.12422.68
30037552539059531.50.20.1228.35
40043061044569531.50.230.11537.79
50049071051080531.50.250.11147.24
63055581558094031.50.280.10859.52