6181Y – BS 6004
- REACH
- RoHS
- CE
- CPR Compliant
Application
The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts. Ideal for internal wiring of appliance.
Standard
BS 6004:2012, EN 50363-3 with BS 7655-4.2 (Only for sheath)
Technical Data
Voltage Rating: 1.5 mm² to 35 mm² – 300 / 500V
Harmonised Designation: -15°C to 70 °C
Minimum Bending Radius:
Upto 10 mm²: 10 X Overall Diameter
16 & 35 mm²: 12 X Overall Diameter
16 & 35 mm²: 12 X Overall Diameter.
Test Voltage: 2 kV for 15 min
Construction
Conductor : Plain annealed copper conductor : 1.5 & 2.5 mm² Class -1, 4.0 to 35 mm² stranded Class 2 complying with BS EN 60228, HD 383, IEC 60228
Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3
Sheath : PVC (Polyvinyl Chloride ) compound type Type 6 complying with BS 7655-4.2
Insulation Colours : Blue and brown
Sheath Colou : Grey RAL 7001
Cabel Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required: 04 – blue, 09 – brown.
Part Number | Nominal Cross Sectional Area (Sq. mm) | Nominal Insulation Thickness (mm) | Nominal Sheath Thickness (mm) | Overall Diameter Lower Limit (mm) | Overall Diameter Upper Limit (mm) | Approx. Net Weight (kg/km) |
01150101xx10 | 1.5 | 0.70 | 0.8 | 4.20 | 5.00 | 37 |
01150102xx10 | 2.5 | 0.80 | 0.8 | 4.80 | 5.70 | 51 |
01150103xx10 | 4 | 0.80 | 0.9 | 5.50 | 6.70 | 75 |
01150104xx10 | 6 | 0.80 | 0.9 | 6.00 | 7.30 | 98 |
01150105xx10 | 10 | 1.00 | 0.9 | 7.30 | 8.80 | 152 |
01150106xx10 | 16 | 1.00 | 1.0 | 8.40 | 10.10 | 220 |
01150107xx10 | 25 | 1.20 | 1.1 | 10.00 | 12.10 | 336 |
01150108xx10 | 35 | 1.20 | 1.1 | 11.10 | 13.50 | 353 |
- For current ratings refer table no. 10-1, for voltage drop refer table no. 10-2.
*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)