6181XY - BS 7889
6181XY - BS 7889 Cross

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

BS 7889.

Technical Data

Voltage Rating: 1.5 mm² to 630 mm² – 600 / 1000V

Harmonised Designation : -15 °C to 90°C

Minimum Bending Radius:

4.0 to 50 mm²: 10 X Overall diameter

70 & 630 mm²: 12 X Overall diameter

Test Voltage: 2 kV 15 min.

Cabel Design Parameters

Part NumberNominal Cross
Sectional Area
(sq, mm)
Nominal
Insulation Thickness (mm)
Nominal Sheath
Thickness
(mm)
Approx. Overal Diameter (mm)Approx. Net
Weight (kg/km)
1160010000440.701.408.0107
1160010000660.701.408.5132
11600100010100.701.409.5181
11600100016160.701.4010.5247
11600100025250.901.4012.0358
11600100035350.901.4013.0466
11600100050501.001.4014.0545
11600100070701.101.4016.0765
11600100095951.101.5018.01022
116001001201201.201.5020.01267
116001001501501.401.6022.01556
116001001851851.601.6024.01928
116001002402401.701.7027.02501
116001003003001.801.8029.03108
116001004004002.001.9032.03923
116001005005002.202.0036.04999
116001006306302.402.2040.06414
  • For current ratings refer table no. 9-1, for voltage drop refer table no. 9-2.