Search results will appear here

FR HSF

  • REACH
  • RoHS
  • CE
FR HSF
FR HSF Cross

FR (Flame Retardant) insulation 70°C | Hazardous substance free | Does not propagate flame & fire.

Application

Flexible single core cable with Flame Retardant PVC insulation. This cable can be used in panels, cabinets, machines and internal wirings with switchgears, relays, controllers, equipments, controls units, etc.

Technical Data

Approvals: IS 694 marked, FIA/TAC

Cable Code: Y (FR)

Voltage Grade: Up to and including 1100V

Conductor: Flexible electrolytic annealed plain copper, class 5, IS 8130

Insulation: FR (Flame Retardant) PVC, IS 5831

Packing: 200 mtr. In polybag packing or 180 mtr. coil packed in protective cartons

Properties

  • Temperature range: -15°C to +70°C
  • Max. short circuit temperature rating: 160°C
  • Self-extinguishing and flame retardant according to IS 10810 P – 61
  • Free from 240+ hazardous substance

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.

Part Number
Nominal Cross
Sectional Area
(sq, mm)
No of Strands/Max. strand dia. (mm)Nominal Insulation Thickness (mm )Maximum Diameter Over insulation (mm)Max. current carrying capacity (A)
02090101xx200.516/0.20.62.65
02090102xx200.7524/0.20.62.88
02090103xx20132/0.20.63.013
02090104xx201.530/0.250.73.417
02090105xx202.550/0.250.84.124
02090106xx20456/0.300.84.830
02090107xx20684/0.300.85.338
02090108xx2010140/0.301.07.052
02090109xx2016126/0.401.08.170
02090110xx2025196/0.401.210.288
02090111xx2035276/0.401.211.7112
02090112xx2050396/0.401.413.9146
02090113xx2070360/0.501.416.0216
02090114xx2095480/0.501.618.2262
02090115xx20120608/0.501.620.2310
02090116xx20150750/0.501.822.5355
02090117xx20185931/0.502.024.9415
02090118xx202401200/0.502.228.4500
02090119xx203001500/0.502.431.0550

Test Parameters

TestTest MethodValues
Limited Oxygen IndexIS 10810 P-58> 29%
Limited Temp. IndexIS 10810 P-64≥ 250 °C