A2XY/2XY-1 CORE

  • REACH
  • RoHS
Wire-A2XY/2XY-1-core
A2XY/2XY-1 CORE Cross

Cable Construction

1.1 kV (A.C) & 1.5 kV (D.C ) to Earth
1 cores AL / CU conductor, XLPE insulated, unarmoured cables as per IS 7098 Part – 1.

Conductor: AL up to 10 Sq. mm conductor are solid Cl. 1 as per IS 8130. And above 10 Sq. mm conductor are stranded round or compact Cl. 2 as per IS 8130 In CU 4 & 6 Sq. mm conductor are solid Cl. 1 or stranded Cl. 2 as per IS 8130. 10 Sq. mm & above stranded round or stranded compact Cl. 2 as per IS 8130

Insulation: Crosslinked polyethylene (XLPE)

Core Color: Red or yellow or blue or black or natural

Outer Sheath: PVC Type ST – 2 as per IS 5831 (Option: FR Type / FRLS Type)

Cable Color: Black (Options: Any other color as per requirement)

Cable Design Parameters

While ordering, in addition to the part number the following details shall also be advised: Conductor Type (Aluminium or Copper) and class of conductor (Cl. 1 or 2). Sheath Type – PVC Type ST – 2 (FR or FRLS). Colour from above technical details.

Part
Number
Nominal Cross
Sectional Area
(Sq. mm)
Nominal Thickness
of Insulation
(mm)
Nominal Thickness
of Outer Sheath
(mm)
Approx.
Overall Diameter
(mm)
Approx. Net Wt. of Cable (kg/km)
AL Cable
A2XY
CU Cable
2XY
111300100016160.71.811125225
111300100025250.91.812170330
111300100035350.91.813205425
1113001000505011.815250550
111300100070701.11.816335750
111300100095951.11.8184251000
1113001001201201.21.8205151250
1113001001501501.42226151520
1113001001851851.62247701880
1113001002402401.72279652415
1113001003003001.823011602980
11130010040040022.23314803800
1113001005005002.22.23618404815
1113001006306302.42.24023506150
1113001008008002.62.44728307840
11130010100010002.82.65136709800
  • For conductor and resistance refer table no. 16-1
  • For capacitances, reactance, short circuit rating refer table no. 16-5, 16-6 and 16-7
  • For current rating refer table no. 16-2